Laserlite
 
Solid Sheet Products
 
Glass Reinforced Sheeting
 
Ventilation Products
 
Store Locator

Enter suburb
or postcode:

Bayer Links
Bayer Sheet Companies
Conditions of Use
Privacy Statement
Imprint
Alsynite Industrial Ventilation
Product Range Features & Benefits Applications Performance & Warranty Technical Data
 
Product Range

To keep air circulating at a comfortable temperature within an Industrial building can be difficult and expensive. Alsynite Roof Ventilators are the inexpensive, reliable and effective ventilation solution. Our roof ventilators have been designed to meet AS 2428.1 (1993) to wind speeds of 200 km/hr and the entry of wind-driven rain at a range of 2.5 l/sec under cyclonic conditions. For cyclonic rated areas special fixings are required. Alsynite offers customers two exciting Roof Ventilation options, which will provide fresh air and comfort all year round.

ALSYNITE ROOFVENT 500 INDUSTRIAL VENTILATOR

Economically Priced – Easy To Install
Variable Pitch Base – For Roofs 0 to 22.5 degrees.
Maintenance Free With No Running Costs
High Performance Aluminium Construction
500mm throat diameter

The Roofvent 500 system has been developed by Alsynite to meet the demanding needs of today’s industrial building market. Economically priced, the Roofvent 500 is maintenance free and rotates freely and reliably due to the quality bearing system employed. The variable pitch base also allows rapid installation as one size fits most industrial roof pitch angles.

ALSYNITE SPINAWAY INDUSTRIAL VENTILATOR

The Alsynite Spinaway Industrial Ventilator is constructed from rust-resistant, lightweight aluminium alloy. Combined with perfectly balanced vertical winds vanes and a whisper quiet double row of stainless steel bearings, the Alsynite Spinaway Industrial Ventilator features a low starting torque for continuous operation in even the lightest of breezes.

The Alsynite Spinaway Industrial Ventilator is available in six sizes with a throat diameter ranging from 150mm to 950mm. This provides a combination to suit every ventilation need.

Features & Benefits
Diameter: Available in 150, 300, 450, 500, 600, 800 and 950mm throat diameters
No Operation Costs: Self contained wind powered design - no operational costs incurred
Reduced Power Costs: Proper ventilation provides a cooler, low humidity working environment, which
reduces the need for costly air conditioning or industrial fans
Reduced Installation Costs: Due to the versatility of the variable pitch throat, installation costs are reduced as one unit fits most industrial applications (0˚ to 22.5˚) - not available for 150, 800 and 950mm units
Reduced Maintenance Costs: Rising damp & humidity causes corrosion of building structures,
painted surfaces, metal fittings and electrical wiring - proper ventilation eliminates these problems
Ventilation Damper: A manually operated vent damper to restrict or stop the air flow is available for
units of 300, 450, 500, and 600mm diameter
15 Year Warranty: Conditions apply
Applications
Industrial And Commercial Skylights
Building Skylight Sidings
Nursery And Retail Areas
Carport And Pergola Covers

 

 

Performance & Warranty
Performance Table (Exhaust Capacity in litres per second at wind speed km/h)
MODEL 150 300 450 500 600 800 950
6 km/h 110 270 480 530 620 1233 1640
12 km/h 210 480 790 870 1104 2131 2840
16 km/h 280 620 990 1090 1420 2730 3650

The performance data above is calculated in accordance with the American Society Of Heating, Refrigeration and Air Conditioning Engineers (ASHRAE). Air change rate must conform to local health
department building codes covering the type of installation.

 

Alsynite Industrial Ventilators are backed by a 15 year performance warranty. Click here for full warranty conditions.

 

Technical Data

CALCULATING THE NUMBER OF VENTILATORS REQUIRED

1 Determine the Volume (VOL) of the building in cubic metres (Length x Width x Height).
2 Dependant on the building type, select the required Air Changes (A/C) per hour, from the table below.
3 From local authority records, determine the typical wind speed 6, 12, or 16km/h. This will establish the exhaust capacity litres per second (refer to table).
4

Calculate

No. of Ventilators =

VOL x A/C x 0.278 _____________ Exhaust Capacity litres per sec

 
(refer to table)
NOTE: 0.278 converts m3/hr to litres/second

 

UNIT DIMENSIONS (mm)
MODEL 150 300 450 600 800 950
Diminsion A 155 305 450 605 800 950
Diminsion B 325 380 415 455 530 600
Diminsion C 330 480 620 770 970 1130

 

 

  © Copyright (2007) Bayer MaterialScience Pty. Ltd. All rights reserved.